Burners IL-GS (gas-heavy oil), IL-GS-T (gas-oil)
SibStrong ® gas burners are manufactured in accordance with international and Russian standards applicable to the production and operation of gas equipment and burners.
All components of the burners of our own production undergo multi-stage quality control.
The applied gas equipment and automation of leading Russian and foreign manufacturers ensures high industrial and environmental safety and stable operation of SibStrong® burners.
Easy operation and maintenance. The design of the burner provides an easy transition from the main type of fuel to the reserve one.
TECHNICAL AND FUNCTIONAL CHARACTERISTICS COMBINED GAS-heavy oil (OIL) BURNERS IL-GS/GS-T
- SibStrong gas burners are manufactured in accordance with international and Russian standards applicable to the production and operation of gas equipment.
- All burner components of our own production undergo multi-stage quality control.
- They operate in a two-stage mode, it is possible to work in a modulating mode - power control is carried out using an electronic regulator installed on the burner control panel.
- The main type of fuel is natural gas, the reserve is heavy oil, oil, light oil.
- The gas-air mixture is formed in the burner tube.
- Used to work with all types of combustion chambers.
- Possibility of the most complete combustion of gas by means of electronic control of the ratio of air and gas.
IL-GS (gas-heavy oil), IL-G2 - two-stage, IL-GS-T (gas-oil), IL-GM - modulating
| IL-GS2 IL-GSM |
Capacity | Oil consumption, gas | Oil consumption, heavy oil | Power consumption | Oill heater | Motor power | Weight without gas ramp, no more |
|---|---|---|---|---|---|---|---|
| IL-5GS2/M | 465-1200 kW/h | 48-125 m³/hour | 42-107 kg/hour | 8,9 kW | 6 kW | 1,5 kW | 90 kg |
| IL-7GS2/M | 600-1800 kW/h | 62-187 m³/hour | 54-161 kg/hour | 14,6 kW | 10,2 | 3 | 120 kg |
| IL-8GS2/M | 700-2900 kW/h | 73-302 m³/hour | 63-260 kg/hour | 20,4 kW | 15 kW | 4 kW | 125 kg |
| IL-8GS2A/M | 700-3200 kW/h | 73-334 m³/hour | 63-287 kg/hour | 20,4 kW | 15 kW | 4 kW | 125 kg |
| IL-9GS2/M | 1000-4000 kW/h | 104-417 m³/hour | 90-359 kg/hour | 29,8 kW | 22,5 kW | 5,5 kW | 223 kg |
| IL-1OGS2/M | 1200-6000 kW/h | 125-520 m³/hour | 107-538 kg/hour | 42,6 kW | 30 kW | 11 kW | 223 kg |
| IL-GS-T2 IL-GS-TM |
Capacity | Oil consumption, gas | Oil consumption, heavy oil | Power consumption | Oill heater | Motor power | Weight without gas ramp, no more |
|---|---|---|---|---|---|---|---|
| IL-5GS-T2/M | 465-1200 kW/h | 48-125 m³/hour | 42-107 kg/hour | 8,9 kW | 70/6 kW | 1,5 kW | 62 kg |
| IL-7GS-T2/M | 600-1800 kW/h | 62-187 m³/hour | 54-161 kg/hour | 13,3 kW | 70/9 kW | 3 kW | 108 kg |
| IL-8GS-T2/M | 700-2900 kW/h | 73-302 m³/hour | 63-260 kg/hour | 17,3 kW | 70/12 kW | 4 kW | 113 kg |
| IL-8GS-T2A/M | 700-3200 kW/h | 73-334 m³/hour | 63-287 kg/hour | 17,3 kW | 70/12 kW | 4 kW | 113 kg |
| IL-9GS-T2/M | 1000-4000 kW/h | 104-417 m³/hour | 90-359 kg/hour | 22,2 kW | 90/15 kW | 5,5 kW | 208 kg |
| IL-10GS-T2/M | 1200-6000 kW/h | 125-520 m³/hour | 107-538 kg/hour | 27,6 kW | 90/15 kW | 11 kW | 208 kg |
* Type of regulation - two-stage modulating
Dimensions (mm)
Power diagrams
COMPLETE BURNERS STANDARD
Burner body, body cover, burner counter-swivel flange, flange seal, burner motor, fan wheel, gas solenoid valve system, light oil burner fuel assembly and nozzles (for IL-GL), control panel with burner control , burner tube with turbulator, air damper with air regulator servo drive (for single-stage burners without servo drive), gas throttle servo drives, oil fuel regulator servo drive (for IL-GM/GLM), ignition transformer, ignition cables, ignition electrodes, ionization electrode, sensor flame, external pumping station (NSh pump), fuel hoses, pressure reducing valve, pressure gauge, gas filter, gas pressure regulator, minimum and maximum gas pressure sensor, safety solenoid valve (for IL-5), shut-off valves of the first and second stages (for IL-7 - IL-10), valve tightness control devices (for IL-7 - IL-10).
ADDITIONAL PACKAGE IS POSSIBLE
- single adapter flange
- double reducer flange
- heat-insulated adapter flange
- non-standard burner tube length
- ball valves with flanged or threaded ends
PERFORMANCE REQUIREMENTS
- Fuel used for combustion in burners: GOST 5542-2014 "Combustible natural gases for industrial and domestic purposes"
- Power supply voltage, nominal: 220-380V, 50Hz
- The amount of emissions of nitrogen oxides and carbon monoxide does not exceed the standards established by the technical regulations of the Russian Federation and is: NOx≤85 mg/kW h; CO≤50 mg/kWh
- Noise level 60-70dB
CONSTRUCTION CHARACTERISTICS
- Aluminum alloy burner body
- A highly efficient fan that ensures reliable operation of the burner, also on boilers with increased pressure in the furnace.
- One three-phase electric motor drives the fan, the second fuel pump.
- One electric servomotor with mechanical cam for air/fuel ratio control on stage burners and two electronically controlled servomotors on modulating burners.
- Automatic control and burner control unit.
- The presence of a flame is controlled by a photo sensor and an infrared sensor.
- Air pressure switch.
- The control unit includes: start/stop, auto/manual and min/max switches, operation indicators, burner and preheater blocking.
- Terminal block for power supply and connection of a thermostat for burner control on I (stage or power controller connection.
- The degree of dust and moisture protection of the burner is IP40.